# 3 · Working with assets

The asset page brings everything about a machine together in one place — its
condition, every sensor on it with a week of trend, whether it's running, its
history, and any open issues. An **asset** is a single piece of equipment (a pump,
a compressor, a genset, a panel), and this chapter walks through its page in
detail, then shows how to read a single measurement point and how to build and
adjust the structure underneath.

## What's on an asset page

Open an asset by clicking its name anywhere it appears — a section or zone page,
*Needs attention*, the Points page, search, or the activity feed. You land on a
page like this.

![An asset page: header, points with a week of trend, and activity](../_images/03-asset.png)

### The header

The header gives you the asset at a glance:

- Its **ISO 10816 class** (`ISO I`) for rotating equipment — the vibration severity
  class for this machine — or its equipment type for anything else.
- Its **name**, and a nameplate line (maker, model, rating) if one has been entered.
- Its current **state** (here, **Warning**) and when it was last **updated**.
- **Edit** (`E`) to change the asset, and **Point** (`P`) to add a measurement
  point.

Where the asset sits — section and zone — is in the breadcrumb at the top right.

### Points

The **Points** section lists every sensor on the asset, **one row per point**,
grouped by type — here **Temperature** and **Vibration**. The heading counts how
many are **in alarm**, and how many are **not reporting**.

Each row shows:

- The point's **location** (*Motor DE*, *Motor NDE*), with a colour swatch that
  matches its dot on the topology diagram.
- Its latest **Value**, in your units.
- **Last 7 days** — a small trend line. Every row in a group shares one scale and
  one time axis (printed above the group, with the group's actual low–high), so
  you can compare sensors directly.
- Its **State**.

**Scrub the week.** Move the pointer over any trend line: a cursor runs through
every row in the group, the time appears above, and each row's Value switches to
that sensor's reading at that moment. It's the quickest way to see what every
bearing on a machine was doing when one of them jumped.

Only alarm readings, the limits, and the latest point are coloured. Readings taken
while the machine was stopped show as faint dots. A point whose live feed has gone
quiet shows a **No data** chip and how long it's been silent. Click any row to open
the point.

### Operation

![The Operation panel: running periods for the day](../_images/03-asset-operation.png)

If the asset tracks whether it's running, the **Operation** panel shows it. The
heading reads the number of periods, whether it's **currently On**, **Off**, or
**Stale**, and when the running signal last pinged. Below it:

- **From → To** — the window to show; today, midnight to midnight, by default.
- A strip of the window, with running and stopped periods drawn differently.
- A table of periods — **State**, **From**, **To**, **Duration** — newest first,
  with **Set ON** / **Set OFF** on the current period to correct it by hand.

Why it matters: some readings — vibration especially — only make sense while the
machine is running. Mechbase knows when the asset was stopped and treats those
readings accordingly (see [Running state and operating hours](#running-state-and-operating-hours)).

### Topology

For rotating equipment, **Topology** is a simple map of the machine — its **body
segments** (non-drive end and drive end of the motor and the driven machine) with
a coloured dot for each measurement point. The same colours are used for the
points and their trend lines, so you can connect a reading to a physical spot on
the machine at a glance.

### Attachments

**Attachments** holds reference **Photos** and **Docs** for the asset — nameplate
shots, drawings, manuals. Click **Add photo** or the document tile to upload; click
any tile to open it full size.

## Notes, activity, and open issues

The right-hand side of the asset page is its conversation and history.

![An asset's activity, with an open non-conformity pinned at the top](../_images/03-asset-activity.png)

**Notes.** The **Add a note…** field at the top expands when you click it. Write
what you saw, optionally open **Reference measurement points** to tag specific
points, and click **Post** (or `⌘ Enter`). You can edit or delete your own notes
later with the pencil and bin icons; deleting shows a short **Undo** so a slip is
never permanent.

**Open issues.** Any **non-conformities** raised against the asset during
inspections are pinned at the top of **Activity**, and the heading counts how many
are **open**. Each shows the failed check (linking to the inspection report), the
route, its severity — **Warning** or **Critical** — and how long it's been open,
with a **Resolve** button. Resolving asks for an optional **Resolution comment**;
click **Mark resolved** and the item closes, with your name and comment on the
record. Non-conformities come from routes — see [Inspections and routes](routes.md).

**Activity.** Below the open issues is the asset's complete history, newest first:

- State changes in plain language — *"Degraded to warning from Motor DE"*, with the
  reason. Changes caused by a reading carry a **fault record ±60 s** link: a page of
  mini-trends showing every sensor on the asset in the minute before and after the
  change, so you can see what moved first.

  ![A fault record: every sensor on the asset, 60 seconds either side of a change](../_images/03-fault-record.png)

- Changes from inspections — *"via inspection"*, with who and when, linking to the
  report.
- **No readings** from a point (and how often it was expected), and **Readings
  resumed** when it comes back.
- Resolved non-conformities, with the resolution comment.

Bursts of changes fold into *"+N earlier changes"* so the list stays readable.

## Measurement points and what each one watches

A **measurement point** is one specific thing you measure, in one specific place on
the asset — the drive-end bearing's vibration, the motor's temperature, the pump
seal's ultrasound. An asset usually has several, and each is named by its
**location**.

Each point has a **type** (its transducer), and Mechbase groups points by type on
the asset page. Mechbase supports a wide range, so you can capture almost anything:

- **Vibration** — overall levels and full waveforms from rotating equipment.
- **Temperature** and **Thermography** — contact temperature and thermal images.
- **Ultrasound** — high-frequency sound, in dB, e.g. from a failing seal or bearing.
- **Pressure**, **Flow**, **Current**, **Voltage** — process and electrical values.
- **Tachometer** and **Counter** — shaft speed and counts.
- **Boolean** — a simple yes/no reading.
- **State** — an on/off signal such as a fault contact or a run lamp, recorded as
  periods (*On since 06:12*) rather than a trend.
- **Production** — whether the machine is running; it drives the Operation panel
  and running hours. It isn't offered when you add a point by hand.

> **Note:** Vibration points only report alarms once the asset has an **ISO 10816
> class** set, since that class defines the severity bands. You set it on the asset,
> and each point can inherit it or override it.

## A point's own page

Click a point to open it. This is where you read its numbers and history.

![A vibration point: headline, signal trends, and the inspect panel](../_images/03-point-detail.png)

At the top you get an honest **headline**: the value that matters for this point
(for vibration, the velocity at 10 Hz, with its relation to the limit — *"Above
warning threshold"*), the other key values beside it, the **current state**, and
when it was **last checked**. If the machine is stopped, the headline says so and
shows the state **at last run** instead of a meaningless stopped reading; if the
feed has gone quiet, it says **No data** and since when.

Alongside:

- **Measurement** (`M`) — record a reading by hand, right there on the page.
- **Edit** (`E`) — change the point.
- **Alarm rules** — see and change the limits ([Measurements, trends, and alarms](measurements.md)).
- **Sources** — where data arrives from automatically (*"Compressor room node, CH 0"*
  or *"MQTT LPG-TM-001, CH 1"*), with a live dot when it's reporting.
- **Run detection** (vibration points) — how this sensor tells running from
  stopped; see [Running state and operating hours](#running-state-and-operating-hours).

Below the headline are the point's trends, and below those the list of readings,
grouped by day and by run. Reading those properly — and the vibration analysis
tools — is the subject of [Measurements, trends, and alarms](measurements.md).

## Running state and operating hours

Mechbase works out on its own whether each machine is running, because so much
depends on it: vibration readings only mean something while the machine runs,
stopped readings shouldn't raise alarms, and running hours drive maintenance
intervals.

It decides in this order:

1. **A tachometer, if the asset has one reporting.** A shaft-speed reading above
   zero means running. While the tachometer has reported in the last ten minutes,
   it has the final say.
2. **A run signal**, such as a contactor or a PLC bit, wired to a MaintNode or sent
   from your own system.
3. **The vibration itself.** Each vibration sensor learns, from its own history,
   the level that separates *idle* from *running* on that machine. The point page
   shows this as **Run detection** — for example *"ON ≥ 0.150 g · default, not
   enough idle and running history yet"* while it's still learning, and the learned
   idle and running levels once it has enough. If a sensor only ever fires when a
   *neighbouring* machine runs, Mechbase says so (*"Not used: … Check where it is
   mounted"*) — usually a sign it's mounted on the wrong machine.

You can always correct the current period by hand with **Set ON** / **Set OFF** in
the Operation panel.

**Operating hours.** Running time accumulates automatically and is totalled on the
**Hours** page ([Finding your way around](navigating.md#running-hours)).
If a machine has a physical hour meter, record its reading on a route or by hand
on the running-hours point: Mechbase takes it as the new total and carries on
counting from there.

## Adding a section, a zone, or an asset

You build out a site from the top down: add **sections**, add **zones** inside
them, then add **assets** inside the zones.

- **Add a section** from the menu, under *Sections → Add a section*.
- **Add a zone** from a section page, using **Add Zone** (`Z`).
- **Add an asset** from the **Add asset** row at the bottom of a zone on the section
  page: type its name in the small **New asset** dialog and click **Add asset**.

The new asset appears in place, ready to fill in. Open it and click **Edit** to set
its type, class, and topology (next section), then add points with **Point**.

> **Tip:** Large sites don't have to be typed in by hand. A room or equipment list
> in Excel can be imported as zones in one go — see
> [Setting up and managing your account](administration.md).

## Editing an asset

Open the asset and click **Edit** (`E`).

![Editing an asset: identity, topology, and baselines](../_images/03-asset-edit.png)

- **Identity** — the **Equipment type**: *Rotating Equipment*, *Electrical
  Equipment*, *Static Equipment*, or *Infrastructure*. Only rotating equipment gets
  an **ISO 10816** class and a machine body.
- **ISO 10816** — the vibration severity class (Class I, small machines, through
  Class IV) that sets the default vibration alarm bands.
- **Topology** — the **Machine body**: the drive-end and non-drive-end segments
  that become the bearing diagram and decide where points sit. Add segments with
  **+ DE**, **+ NDE**, or a **Custom…** name, in order along the shaft.
- **Baselines** — for each vibration point, the learned "normal" that relative
  alarms compare against. **Clear** reverts a point to the basic ISO alarm;
  **Create from date…** relearns it from a date you pick — useful after a repair,
  or to escape a period of bad data. Mechbase tells you how many usable readings
  there are since that date (it needs 100) before you commit.

Click **Save** to keep your changes.

> **Heads-up:** **Delete asset** removes the asset with all its points and
> history. An asset that already has recorded readings can only be deleted by a
> staff user, who must type the asset's name to confirm.

## Adding and editing a measurement point

On an asset page, click **Point** (`P`). A small dialog asks for the **Transducer
type**, the **Location** (*"e.g. Motor, Bearing 1"*), and — for rotating equipment —
where it sits on the machine body. Click **Add point** and it appears in the list.

![Adding a measurement point](../_images/03-point-create.png)

To change a point, open it and click **Edit** (`E`). The edit page is one
scrollable form:

![The measurement-point edit form](../_images/03-point-edit.png)

- **Identity — where the sensor sits.** The free-text **Location** (*Motor DE*),
  and optionally the **Body segment** (NDE/DE) and **Body angle** (top, horizontal,
  bottom, axial) so Mechbase knows exactly where on the machine the sensor is.
- **Sensor — transducer and unit.** The **Transducer type**, the **Unit** the
  sensor records in (the unit *you* see is set in your profile), and the **ISO 10816
  class** (inherit from the asset, or override).
- **Shaft & bearing** (vibration points). The **Nominal speed** in RPM from the
  nameplate; the **Bearing** fitted at this point, picked from the bearing library
  ([Measurements, trends, and alarms](measurements.md#bearings-and-defect-frequencies));
  a **Speed ratio** if the bearing sits behind a gearbox or belt; and the
  **Envelope band** used to demodulate bearing faults (500 Hz–10 kHz if left blank).
- **Instructions.** Rich-text guidance shown to whoever takes a reading here — on
  the web and on the phone. Worth filling in for anything non-obvious: where to put
  the probe, which axis, what to watch for.
- **Photo.** A reference image of where the sensor goes, shown next to the
  instructions.
- **Sources.** Where automatic data comes from (next section).

**Save changes** (Enter) keeps your edits. **Delete point** removes it after a
confirmation.

> **Heads-up:** Deleting a point removes its readings and history too. If you only
> want to stop using it, consider whether editing is enough before you delete.

> **Tip:** Good instructions make field readings consistent. For vibration, say
> where the load zone is and which way the sensor's X axis points; for
> thermography, say what to compare against (the other phases, the twin bearing);
> for ultrasound, say which probe and how hard to press. The same spot, the same
> way, every visit.

## How a point gets its data: sources

A point can be fed two ways.

**By hand.** Anyone taking a reading — on the web with **Measurement**, or out in
the field on the mobile app — records the value directly. The **instructions** above
are there to make those manual readings consistent.

**Automatically, from a source.** At the bottom of the edit page, **Sources** lists
the live feeds connected to this point. Each row shows where the data comes from —
a **MaintNode** device, its acquisition group and channel, and the sensor type; or
an **MQTT** device and channel — and when it last reported. Click **Add source** to
connect one, or the pencil to change it.

![A point's Sources: one MaintNode channel](../_images/03-point-sources.png)

These automatic sources are how MaintNode devices and your own systems feed
readings straight into Mechbase without anyone typing them in — covered in
[MaintNode devices and automatic data](maintnode.md).

Whichever way a reading arrives, it's treated the same: it's added to the point's
history, checked against the alarm limits, and — if it crosses one — it updates the
asset's state and shows up in the activity feed.